This valve is widely used in petroleum,chemical,pharmaceutical,power and otherindustries,for opening andclosingusedin steam,water,oil mediumpipeline on.
Technical data
产品型号 Product model | SZ45T | SZ45W | SZ45T | SZ45W | |
公称压力PN(MPa) Nominal pressure | 1.0 | 1.6 | |||
试验压力 Test pressure | 强度(水)(MPa) Strength(water) | 1.5 | 2.4 | ||
密封(水)(MPa) Seal(water) | 1.1 | 1.76 | |||
工作温度(℃) Temperature working | ≤200 | ≤100 | ≤200 | ≤100 | |
适用介质 Suitable working | 水、蒸气 Water,steam | 油品Oil | 水、蒸气 Water,steam | 油品Oil | |
Meterial of main parts
零件名称 Part name | 材料Matenal | |
SZ45T-10/16 | SZ45W-10/16 | |
闸板Gate disc | 灰铸铁+黄铜 Cast iron +Brass | 灰铸铁Cast iron |
阀体、阀盖 Body,bonnet | 灰铸铁Cast iron | 灰铸铁Cast iron |
阀杆Stem | 碳钢、黄铜、不锈钢 Carbon steel,brass, stainless steel | 碳钢、黄铜、不锈钢 Carbon steel,brass, stainless steel |
阀杆螺母Stem nut | 黄铜、球墨铸铁 Brass,nodular cast iron | 黄铜、球墨铸铁 Brass,nodular cast iron |
手轮Handwheel | 灰铸铁Cast iron | 灰铸铁Cast iron |
Main dimensions
DN (mm) |
L |
D |
D1 |
D2 |
b-f |
Z-φd |
A |
K |
H |
40 | 165 | 145 | 110 | 85 | 18-3 | 4-φ18 | 65 | 32 | 300 |
50 | 178 | 160 | 125 | 100 | 20-3 | 4-φ18 | 65 | 32 | 355 |
65 | 190 | 180 | 145 | 120 | 20-3 | 4-φ18 | 65 | 32 | 360 |
80 | 203 | 195 | 160 | 135 | 22-3 | 4-φ18 | 65 | 32 | 400 |
100 | 229 | 215 | 180 | 155 | 22-3 | 8-φ18 | 65 | 32 | 428 |
125 | 254 | 245 | 210 | 185 | 24-3 | 8-φ18 | 65 | 32 | 513 |
150 | 280 | 280 | 240 | 210 | 24-3 | 8-φ23 | 65 | 32 | 565 |
200 | 330 | 335 | 295 | 265 | 26-3 | 8-φ23 | 65 | 32 | 660 |
250 | 380 | 390 | 350 | 320 | 28-3 | 12-φ23 | 65 | 32 | 907 |
300 | 420 | 440 | 400 | 368 | 28-4 | 12-φ23 | 70 | 48 | 920 |
350 | 450 | 500 | 460 | 428 | 30-4 | 16-φ23 | 70 | 48 | 1036 |
400 | 480 | 565 | 515 | 482 | 32-4 | 16-φ25 | 70 | 48 | 1177 |
450 | 510 | 615 | 565 | 532 | 32-4 | 20-φ25 | 70 | 48 | 1246 |
500 | 540 | 670 | 620 | 585 | 34-4 | 20-φ25 | 70 | 48 | 1395 |
600 | 600 | 780 | 725 | 685 | 36-5 | 20-φ30 | 70 | 48 | 1590 |
Non-Rising Stem Cuniform Underground Gate Valve: Complete Guide
The non-rising stem cuniform underground gate valve is a widely used industrial valve designed for underground pipeline applications where overhead space is limited. With a cuniform wedge gate structure and non-rising stem design, it ensures reliable shut-off, long service life, and efficient operation even in demanding environments.
This article provides a comprehensive overview of its warranty terms, maintenance methods, certification standards, and available specifications, making it a valuable reference for engineers, procurement teams, and end-users.
Compact non-rising stem design, suitable for confined underground spaces.
Cuniform wedge ensures tight sealing under high pressure.
Robust body with anti-corrosion coating for extended durability.
Widely applied in municipal water supply, wastewater management, oil & gas, and industrial networks.
Compliance with international safety and environmental standards.
Manufacturers of non-rising stem cuniform underground gate valves usually provide clear warranty coverage to protect end-users. Below are typical warranty conditions:
Warranty period: 12–24 months from delivery or 18 months from installation, whichever comes first.
Scope of coverage: Manufacturing defects, material faults, or malfunction under normal operating conditions.
Exclusions:
Damage due to improper installation or misuse.
Corrosion caused by exposure to non-specified fluids.
Unauthorized modifications or repairs.
Some suppliers offer extended warranties with service agreements, including:
Regular inspection visits.
Priority access to spare parts.
On-site technical support for urgent issues.
Proper maintenance ensures long-lasting performance of underground gate valves. The following practices are recommended:
| Inspection Item | Frequency | Method |
|---|---|---|
| Valve body and coating | Every 6 months | Check for corrosion, cracks, or external damage. |
| Stem operation torque | Quarterly | Test opening/closing for smooth operation. |
| Sealing performance | Annually | Pressure test to confirm zero leakage. |
| Packing and gaskets | Annually | Replace if leakage or wear is detected. |
Apply anti-corrosive lubricant on the stem and operating nut.
Ensure lubrication channels are free from dust and debris.
Use manufacturer-approved grease to avoid chemical incompatibility.
Operate the valve at least once every 3 months to prevent jamming.
Install valve boxes or extension rods for underground accessibility.
Record all inspection and maintenance activities for future reference.

To meet global industry requirements, the non-rising stem cuniform underground gate valve complies with multiple standards:
ISO 9001 – Quality management system compliance.
EN 1074 / EN 1171 – European standards for water supply valves.
API 600 / API 6D – American standards for industrial valves.
WRAS / NSF – Drinking water safety certification.
CE Marking – Compliance with EU directives.
ISO 14001 – Environmental management compliance.
RoHS Directive – Restriction of hazardous substances in materials.
Energy-efficient design ensuring minimal torque and lower energy use.
The non-rising stem cuniform underground gate valve is available in multiple models and sizes to meet different project needs.
| Parameter | Details |
|---|---|
| Valve type | Non-rising stem Cuniform gate valve |
| Installation method | Underground, with extension rod optional |
| Nominal diameter (DN) | DN50 – DN1200 |
| Pressure rating | PN10, PN16, PN25 |
| Body material | Ductile iron, cast steel, or stainless steel |
| Wedge material | Ductile iron with rubber coating (EPDM/NBR) |
| Stem material | Stainless steel / carbon steel |
| Coating | Fusion bonded epoxy (FBE), anti-corrosion |
| Operation | Manual handwheel, gearbox, or electric actuator |
| Mediums handled | Water, wastewater, oil, gas, non-corrosive fluids |
| Working temperature | -10°C to +80°C (customization available) |
Correct operation is essential for maximizing the performance of underground valves.
Installation Preparation
Ensure pipe ends are clean and aligned.
Confirm pressure rating compatibility.
Apply protective coating before burying.
Operation Guidelines
Rotate handwheel or actuator smoothly; avoid sudden force.
Ensure valve is fully closed/opened as required.
Do not exceed rated torque during operation.
Storage Conditions
Store in a dry, ventilated area before installation.
Keep valve ends sealed with protective covers.
Avoid direct exposure to sunlight and corrosive chemicals.
Reliable after-sales service is crucial for customer satisfaction. Leading manufacturers provide:
Technical documentation (manuals, CAD drawings, test reports).
On-site installation support for large projects.
24/7 technical hotline for troubleshooting.
Training programs for maintenance teams.
The non-rising stem cuniform underground gate valve is a highly reliable choice for underground pipelines where space is limited. With strong sealing performance, compliance with international certifications, and options for customized specifications, it serves as an ideal solution for municipal water supply, wastewater treatment, oil and gas, and industrial networks.
By following proper maintenance methods, adhering to certification standards, and leveraging manufacturer after-sales support, operators can ensure long-term reliability and cost-effective performance of their valve systems.
This website uses cookies to ensure you get the best experience on our website.